Admin

TE804

 

MAIN TECHNICAL CHARACTERISTICS

  • Operating temperature -20 - +60°C
  • Storage temperature -30 - +80°C
  • Power supply from 9-to 33Vdc
  • Voltage input measuring range 50/620Vac
  • Frequency range 45 - 65Hz
  • Front panel protection rating IP64
  • Measuring precision ±1% - ±1 digit
  • Type of measurement :True effective value (RMS)
TE804

TECHNICAL CHARACTERISTICS

LCD Graphic Display 192x64 pixel, 95X45 mm With backlight

 

With built-in LED :

  • Test-Aut-Man-Reset-Help-Mains Contactor & Generator Contactor

 

Key only

  • Start-Stop

 

6 PROGRAMMING KEYS

  • Enter-Exit-Scroll Parameters ▲▼-Increase and Decrease Parameters

 

INDICATOR LEDS

  • Engine running
  • Generator powered
  • Mains powered
  • Mains contactor closed
  • Generator contactor closed
  • Help message
  • Test key pressed
  • Automatic key pressed
  • Manual key pressed
  • Reset key pressed

 

 

Large size graphical Display

By displying at the same time of 8 typical values and character dimension of 10mm

sample: 3 voltages- 3 currents- frequency kVA

Note “Mains” or “Generator” appears on the display to point out to which unit the aspects displayed refer to:

  • Battery voltage
  • Mains and phase generator voltages, between the lines of the system
  • Phase currents
  • Phase and total active, reactive and apparent powers
  • Active, reactive and apparent energy
  • P.F.- Power factor of each phase
  • Energy meter
  • Frequency
  • Oil pressure instrument
  • Water temperature instrument
  • Fuel level instrument
  • Engine RPM
  • Number of total starting attempts
  • Percentage of successful starting attempts
  • Total hours of use
  • Partial hours of use
  • Hours left to maintenance
  • Internal hour counter (not resettable) to find real hours of use

HELP KEY(BUILT-IN LED)

By pressing the help button (in case of alarm) the operator will be able to see on the display all information about alarm and assistance

ENGINE CONTROL INSTRUMENTS

  • Fuel level
  • Temperature
  • Oil pressure
  • RPM meter

LIST OF ALARMS

  • Engine temperature warning
  • (Analogue sensor)
  • High engine temperature (Analogue sensor)
  • Temperature analogue sensor fault
  • High engine temperature (digital sensor)
  • Oil pressure warning (analogue sensor)
  • Low oil pressure (analogue sensor)
  • Pressure analogue sensor fault
  • Low oil pressure (digital sensor)
  • Pressure digital sensor fault
  • Fuel level warning (analogue sensor)
  • Low fuel level (analogue sensor)
  • Level analogue sensor fault
  • Low fuel level (digital sensor)
  • High battery voltage
  • Low battery voltage
  • Inefficient battery
  • Battery charger alternator failure
  • ”W” signal failure
  • Low engine rpm
  • High engine rpm
  • Starting failure
  • Emergency stop
  • Unexpected stop
  • Engine stop failure
  • Low generator frequency
  • High generator frequency
  • Low generator voltage
  • High generator voltage
  • Generator asymmetry
  • Generator short-circuit
  • Generator overload
  • External generator protection
  • Switch tripped
  • Incorrect generator phase sequence
  • Incorrect mains phase sequence
  • Wrong system frequency setting
  • Generator contactor failure
  • Mains contactor failure
  • Maintenance request in a number of steps
  • System error
  • Fuel transfer empty
  • Fuel transfer too full
  • Rent hours exausted
  • Low radiator liquid level

VARIOUS FUNCTIONS

  • 1 RS232 port for: SETUP board, Remote Control, Connection to traditional modem, GSM modem, GPS system, communication protocol MODBUS, communication by LAN/ETHERNET.
  • Standard EJP function (for the French market)
  • EJP/T function (for the French market)
  • SCR function (generator start and
  • switchover also in the presence of voltage by an external signal)
  • Gas engine function
  • Decelerated starting and stopping function
  • Sparkplugs pre-heating function
  • Keyboard lockout function
  • Generator start function according to the users kW
  • Fuel topping up pump control function by 4 levels sensor
  • Rental function that can be set by hours
  • Dummy load control function
  • Restore function by issuing a programmable relay of the state of the card operating mode (e.g. reset or cycle state, etc.)
  • Possibility to lock all the functions at a given number of working, maintenance or rental hours
  • Daily, weekly or monthly automatic test External Start
  • External Stop
  • 8 programmable user’s alarm
  • 3 different global alarm with indipendent programmation

 

Main technical characteristics

  • Operating temperature -20 +60°C
  • Storage temperature -30+80°C
  • Power supply from 9-to 33Vdc
  • Voltage input measuring range 50/620Vac
  • Frequency range 45 - 65Hz
  • Front panel protection rating IP64
  • Measuring precision ±1% - ±1 digit
  • Type of measurement :True effective value (RMS)
Download Catalogue